22 PSE Series Instruction Manual — P/N LS10227-000NF-E:B 3/29/2021
Section 3: Programming Options
This section describes the programming options available via DIP switch settings. The PSE can be field programmed using DIP switches
S1-S8 which are located at the bottom of the circuit board. S1 controls the global options of the power supply and S2-S8 control the
functions of each output circuit, respectively. Refer to the following illustration for switch locations and DIP switch placement in the ON
and OFF positions.
Important: Activate output DIP switch changes by setting S1 positions 9 and 10 appropriately. Refer to Table 3.6 on page 24 for DIP
Switch programming settings.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as
indicated below:
Program feature or
option
Permitted in
UL864/2572 and
ULC S527? (Y/N)
Possible settings
Settings
permitted in
UL 864/ UL2572
Settings
permitted in
ULC S527
Door Holder Dropout
Delay
Y Refer to “AC Loss Door Holder Dropout Timer” on
page 24.
Does not drop
15 seconds
5 minutes
60 seconds
Does not drop
15 seconds
60 seconds
5 minutes
Does not drop
15 seconds
60 seconds
5 minutes
AC Loss Delay Timer Y Refer to “AC Fail Indication Delay” on page 24.
30 hours
12 hours
2 hours
none
2 hours
1
none
1 A two hour delay is only permitted on an addressable FACP.
2 hours
none
Table 3.1 Agency-Permitted Programming Settings
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8
TB15
Switches 1 through 7 shown
in OFF (Open) position
Switch 8 shown in
ON (Closed) position
Figure 3.1 Field Programming DIP Switches
Switch 10 shown in
ON (Closed) position
Switches 1 through 9 shown
in OFF (Open) position
S1
S2-S8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER PSE-10 and is the answer not in the manual?

Honeywell NOTIFIER PSE-10 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER PSE-10
CategoryExtender
LanguageEnglish

Related product manuals