76 RP-2002 Series Manual — P/N 53039:E6 1/26/2017
Programming Master Programming Level
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.
3.5.10 Clear Program
Pressing 1 while viewing Programming Screen #4, will select the Clear Program option. The
control panel will provide a warning to the user by prompting with the following display:
Pressing 1 for Yes will cause the control panel to carry out the selected clear option. Pressing 2 for
No will prevent programming from being cleared.
3.5.11 Password Change
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 2 while viewing Programming Screen #4 will
cause the following screen to be displayed:
Press 1 to change the Master Programming Level password or 2 to change the Maintenance Level
password. Note that the passwords will not
be displayed on annunciators.
The following screen will appear when either change option is selected:
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
The new five digit password must be re-entered to accept the change. The display will then return
to the initial Password Change Screen.
WALKTEST EVENTS
PROGRAMMING
1=CLEAR PROGRAM
2=PASSWORD CHANGE
Programming Screen #4
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES 2=NO
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
Password Change Screen
ENTER NEW FIVE DIGIT
PASSWORD
Enter Password Screen
VERIFY NEW
PASSWORD
Password Change Screen

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER RP-2002C and is the answer not in the manual?

Honeywell NOTIFIER RP-2002C Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER RP-2002C
CategoryControl Panel
LanguageEnglish

Related product manuals