PW7K1R1E Wiring and Setup
Specifications
PW7K1R1E OSDP Reader Interface, Configuration, and Installation Guide, Document 800-26498 19
To further enhance network security, options are available to disable Zeroconf
discovery, as well as the web configuration module itself.
2.15 Specifications
The interface must be used in low voltage, class 2 circuits only.
The installation of this device must comply with all local fire and electrical codes.
Power Input PoE Power Input 12.95W, compliant to IEEE 802.3af
- OR -
PoE+ (25 W), compliant to IEEE 802.3at
- OR -
12VDC +_10%,1.7 A maximum
Power Out-
put
PoE: VO (TB4-1) and RVO (TB7-4), combined: 12 VDC
@.66 A maximum PoE+
-OR-
12 VDC: VO (TB4-1) 12 VDC @ 1 A maximum, RVO,
(TB7-4) 12 VDC @.5 A maximum
Reader
Interface
Reader (TB7-4) 12 VDC @ .5A maximum
Reader (RVO) 12 VDC @.5A maximum
Output Four relays, Form-C contacts rated at 2 A @ 30 VDC
Inputs Six unsupervised/supervised, End of Line resistors, 1k/1k
ohm, 1%, ¼ watt
Standard
Reader Interface
Reader Power: 12VDC @ 5A maximum (RVO,TB7-4)
Communication:
2-Wire RS-485, OSDP protocol, four
devices maximum
RS-485 Mode 9600 bps
Asynchronous
Half-duplex
1 start bit
8 data bits
1 stop bit
Maximum cable length 4000' (1,200m)
Cable requirements
Communication Ethernet
Category 5 minimum