49
MAN0530 Issue 09 October 03 Searchline Excel
2104M0506
3. INSTALLATION AND OPERATION
The following message is then displayed:
Press Enter to
Release 4-20
(14) Press Enter on the keypad.
The following message is displayed for three seconds:
4-20 Released
The display then changes to show the Calibrate menu. The Searchline Excel gas detector
is now live.
This completes the final part of the gas detector alignment procedure.
3.7.6 Finishing Up
To finish the alignment process carry out the following procedure:
(1) Select Power Off from the Interrogator Main menu.
(2) Press (Enter) on the keypad.
Alternatively press the and ESC buttons simultaneously for a fast power off.
Notes:
1. The SHC1 Handheld Interrogator powers down automatically after five minutes of non-use.
2. Fast power off and auto power off are disabled when any menu option is selected that
modifies the unit’s configuration.
(3) Disconnect the Interrogator from the gas detector, reversing the process described at
the beginning of section 3.7.5.
3.8 SYSTEM CONTROLLER CALIBRATION
This procedure is used to set up the system controller using the Searchline Excel gas detector.
A chosen fixed output signal is sent from the Excel gas detector to the system controller allowing
calibration of the 0 - 100% scale of the controller without having to use gas. The steps use
procedures described in the previous section.
To calibrate the controller carry out the following procedure:
(1) Connect the Interrogator to the gas detector.
See Connecting the Interrogator to Searchline Excel Gas Detector.
(2) Turn on the Interrogator.
See Powering Up.
(3) Select Calibrate from the main menu.
Press the up and down keys on the keypad to navigate through the menu options.
(4) Press Enter on the Interrogator keypad and the Calibrate menu is displayed.
(5) Select Force 4-20 from the Calibrate menu.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Searchline Excel Open-Path and is the answer not in the manual?

Honeywell Searchline Excel Open-Path Specifications

General IconGeneral
BrandHoneywell
ModelSearchline Excel Open-Path
CategoryGas Detectors
LanguageEnglish

Related product manuals