76
MAN0530 Issue 09 October 03 Searchline Excel
2104M0506
The second line shows the gas reading and measurement units along with a gas detector
status indicator.
The status character at the end of the second line indicates one of the following:
/ - Normal Operation
A spinning line shows the unit is in the fully active state.
- Inactive State
A stationary line shows the unit is in the inactive state.
w - Active Warning
F - Active Fault
B - Beam Blocked
(7) Switch off the Interrogator (see section 3.7.7 Finishing Up) and disconnect it from the
gas detector.
5.5 ALIGNMENT TELESCOPE
To clean the telescope lens/mirror:
(1) Moisten the surface of the lens/mirror by breathing on it.
(2) Using a soft tissue or lens cloth, lightly wipe the lens/mirror dry with a minimum number
of strokes.
The wiping material may be slightly dampened with a lens cleaning fluid as sold in any
camera store.
5.6 OPERATIONAL MAINTENANCE (FM)
As required as a criterion for the FM Performance Approval, routine operational verification is
recommended once within a three month period and is required once within a six month period
using one of the following methods.
WARNING
The following procedure will indicate a gas reading. Ensure all required personal
have been notified prior to starting and completing the procedure.
Following the procedure described in section 5.1.2 insert a known test filter in the beam
path. Record the response to the test filter and verify that the response is within the
tolerance for stability and repeatability.
Following the procedure described in section 5.1.3, test the unit s response to high %V/V
gas in a gassing cell. Verify that the response is within the tolerance for stability and
repeatability.
For Cross-Duct units, follow the procedure described in section 4.7.2 and verify that the
response to high %V/V gas introduced into the gassing cell is within the tolerance for
stability and repeatability.
5. MAINTENANCE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Searchline Excel Open-Path and is the answer not in the manual?

Honeywell Searchline Excel Open-Path Specifications

General IconGeneral
BrandHoneywell
ModelSearchline Excel Open-Path
CategoryGas Detectors
LanguageEnglish

Related product manuals