Mounting Structure Requirements
● The mounting structure where the SUN2000 is installed must be reproof.
● Do not install the SUN2000 on ammable building materials.
● The SUN2000 is heavy. Ensure that the installation surface is solid enough to
bear the weight load.
● In residential areas, do not install the SUN2000 on drywalls or walls made of
similar materials which have a weak sound insulation performance because
the noise generated by the SUN2000 is noticeable.
4.3.2 Space Requirements
Installation Angle Requirements
The SUN2000 can be wall-mounted or pole-mounted. The installation angle
requirements are as follows:
● Install the SUN2000 vertically or at a maximum back tilt of 15 degrees to
facilitate heat dissipation.
● Do not install the SUN2000 at forward tilted, excessive back tilted, side tilted,
horizontal, or upside down positions.
Figure 4-1 Installation tilts
Installation Space Requirements
● Reserve enough space around the SUN2000 to ensure sucient space for
installation and heat dissipation.
SUN2000-(8KTL-20KTL)-M2
User Manual 4 Installation
Issue 11 (2023-02-07) Copyright © Huawei Technologies Co., Ltd. 27