Table 107. Noise emissions (Maximum configuration)
1
Acoustical characteristics Idling Operating
L
WAd
6.1 bels 6.1 bels
1. The noise emission level that is stated is the declared (upper limit) sound power level, in bels, for a random
sample of servers. All measurements are made in accordance with ISO 7779 and reported in conformance with
ISO 9296.
7063-CR1 Hardware Management Console specifications
Hardware specifications for model 7063-CR1 provide detailed information for your Hardware
Management Console (HMC), including dimensions, electrical, power, temperature, environmental
specifications, and noise emissions.
The HMC controls managed systems, including the management of logical partitions and the use of
capacity on demand. Using service applications, the HMC communicates with managed systems to
detect, consolidate, and send information to IBM for analysis. The HMC provides service technicians with
diagnostic information for systems that can operate in a multiple-partitioned environment.
Use the following specifications to plan for your HMC.
Table 108. Dimensions
Width Depth Height Weight
437 mm (17.2 in.) 705.3 mm (27.76 in.) 43.0 mm (1.7 in.) 14.5 kg (32 lb)
Table 109. Electrical
1, 2
Electrical characteristics Properties
Maximum measured power 300 W
Maximum kVA 0.330
Maximum thermal output 1024 BTU/hr
Input voltage 100 - 127 V ac or 200 - 240 V ac
Frequency 50 or 60 Hz
1. Preliminary data is subject to change.
2. Power consumption and heat output vary depending on the number and type of optional features that are
installed and the power-management optional features that are in use.
Table 110. Environment requirements
Environment
Recommended operating
requirements
Allowable operating
requirements
Nonoperating
requirements
ASHRAE class A2
Airflow direction
1
Front-to-back
Temperature
2
18°C - 27°C (64°F - 80°F) 10°C - 35°C (50°F - 95°F) 5°C - 45°C (41°F - 113°F)
Humidity range 5.5°C (42°F) dew point (DP)
to 60% relative humidity
(RH) and 15°C (59°F) dew
point
20% - 80% RH 8% - 80% RH
Maximum rate of change 5°C/20 hrs
Maximum dew point 21°C (70°F) 27°C (80°F)
Maximum operating
altitude
3050 m (10000 ft)
82 Site and hardware planning

Table of Contents

Other manuals for IBM 8408-44E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM 8408-44E and is the answer not in the manual?

IBM 8408-44E Specifications

General IconGeneral
BrandIBM
Model8408-44E
CategoryServer
LanguageEnglish

Related product manuals