24 Using the system
Fire detection and extinguishant system
The left side of the section reached shows the description of
any faults in progress.
On the right side are the function keys relating to the remote
communicator. Activation or access to these depends on the
access level of the user.
Disable/Enable alarm calls, button to disable/enable
remote communications generated by alarm signals.
Disable/Enable fault calls, button to disable/enable remote
communications generated by fault signals.
Disable/Enable other calls, button to disable/enable
remote communications generated by signals other than
alarm or fault signals.
Stop alarm calls, button to cancel the queue of remote
communications generated by alarm signals.
Stop fault calls, button to cancel the queue of remote communications generated by fault signals.
Disable/Enable other calls, button to cancel the queue of remote communications generated by signals other than
alarm or fault signals.
Stop all calls: button to cancel all remote communications in the queue.
Inim Cloud: This function becomes available via:
Manage System > select one of the available control panels > Communicator
6.4 Managing the extinction channel
The front plates of control panels from the Previdia Compact range equipped with fire extinction channels, provide
signals via the LED indicators:
From the “Extinction” section, which can be reached via the system viewing menu by means of the System status button
(paragraph 5.3), it is possible to access the extinction channel management page.
LED Colour On solid Flashing
Extinction channel
activation LED
Red
Discharge extinguishing agent
activated
Pre-extinguishing time in
progress, imminent discharge
of extinguishing agent
Automatic activation
indicator LED
Red
Extinguishing agent discharge
command activated by
automatic detectors
Extinguishing agent discharge
command partially activated
by automatic detectors
(condition not yet sufficient
for activation of the discharge
procedure)
Bypass automatic
activation LED
Yellow
The automatic discharge
command has been disabled.
The extinction channel can
only be activated manually.
/
Bypass extinction
channel LED
Yellow Channel bypassed /
Manual stop extinction
LED
Yellow
Stop extinction command
activated manually
Fault on stop-extinction circuit
Stop extinction LED
from non-electrical-
devices
Yellow
Stop extinction command
activated by a non-manual
device
Fault on stop-extinction circuit
GSM module trouble
Disable calls
Stop calls
Esc
Access
level:2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INIM Electronics PREVIDIA-C-REP and is the answer not in the manual?

INIM Electronics PREVIDIA-C-REP Specifications

General IconGeneral
BrandINIM Electronics
ModelPREVIDIA-C-REP
CategoryControl Panel
LanguageEnglish

Related product manuals