Programming Manual
48 Power supply settings
Chapter 16
Power supply settings
16.1 How to program the power supply
FROM COMPUTER
Go to SmartLoop System, Control panel x, Power supply, System Programming
This option will allow you to set the operating parameters of the control panel power-supply and
enquirie regarding the minimum battery capacity required to satisfy the system needs during mains
failure (specified in hours).
16.1.1 Parameters
FROM PANEL
Not available.
Mains fault signal
delay
This is a delay between the start of a mains failure event and the respective fault
signal. This delay avoids unnecessary signaling of brief 'Mains failure' events.
After Mains restore
disable battery test
This is the period between mains electricity restoral (during which time the
battery test will be inhibited) and the moment the control panel starts monitoring
the battery efficiency again. Used to suspend the periodic battery-efficiency test,
that may fail if the batteries are recharging.
Battery capacity
calculation
Data the operator must enter in order to allow the system to calculate the
minimum battery requirements.
Stand by Autonomy This is the power autonomy required by the
system in the event of mains failure when the
control panel is in standby status.
Alarm Autonomy This is the battery autonomy required by the
system in the event of mains failure when the
control panel is in Alarm status, once the
Standby autonomy has run out.
Additional loads in stand by This is the current consumption of external
loads (devices connected to the AUX and AUX-
R outputs) when the control panel is in
standby status.
Additional loads in Alarm This is the current consumption of external
loads (devices connected to the AUX and AUX-
R outputs) when the control panel is in Alarm
status.
Battery efficiency factor This is the co-efficient that represents the
battery efficiency status (e.g. New
battery=1).
Minimum battery
size needed
Select Calculate to ask the system to calculate the minimum capacity
requirements, and the typ e of battery to install.

Table of Contents

Other manuals for INIM Electronics SmartLoop

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INIM Electronics SmartLoop and is the answer not in the manual?

INIM Electronics SmartLoop Specifications

General IconGeneral
BrandINIM Electronics
ModelSmartLoop
CategoryControl Panel
LanguageEnglish

Related product manuals