5.4 Sequence for Input terminal functions while Initial Lift start-Up
Running Contactor Feedback
(SW)
If X2 LED off, then the
drive gives Err36
Brake Contactor Feedback (BY)
If X2 LED off, then the
drive gives Err37
Inspection mode input signal
OFFInspection mode
ONNormal Mode
Inspection mode UP signal
For UP direction
command in INS mode
Inspection mode DOWN signal
For DOWN direction
command in INS mode
UP direction limit signal
UP and Down Limit and
Slow down Switches
must be connected for
Inspection run and for
motor tuning
Down direction limit signal
Up terminal slowdown signal
Down terminal slowdown signal
FX-Shorting Contactor Feedback
signal
Applicable for high
power PMSM Gearless
machine. Err29 if X19
LED is OFF
RCR- Manual Door Retiring
Cam Contactor Feedback signal
Applicable for Manual
Door only
ARD function-UPC contactor
Feedback Signal
Safety Circuit feedback signal
(110VAC Input)
If all the field safety
circuits are not ok and
X25 LED is OFF, then
the display shows Err41
Door lock safety circuit feedback
signal1(Car Door) (110VAC
Input)
If Car door is safely
closed, then X26 LED
gets ON
Door lock safety circuit feedback
signal2(Landing Door) (110VAC
Input)
If All landing doors are
safely closed, then X27
LED gets ON