● In the project tree, choose Online access, find the network card corresponding to your computer.
● Double-click Update accessible devices, and wait for a period of time. All the devices scanned in the
network are displayed.
● Find and click the option corresponding to DA200 drive.
(Note: If DA200 drive is used for the first time, it does not have a device name, but its MAC address can be
scanned.)
● Double-click Online & diagnostics to enter the online commissioning state.
● Choose Functions > Assign PROFINET device name.
● Set parameters, and click Assign name.
● Note: The PROFINET communication card name that is online set must be the same as the PROFINET
communication card name that is set during project configuration. Otherwise, devices cannot
communicate through PROFINET.
● Click Assign name to assign device names. (Note: The device name invt-1 is used for example, which
must be the same as the device name configured on the PROFINET communication card in the project.)