3. Connect the power cables to the power supplies.
Table 26 on page 112 identifies the cabling requirements.
Table 26: CTP Power Supply Cables and Wires Needed
ToFromCable/Wire
Termination groundPDU ground terminalOne 18-AWG ground wire
Appropriate leads on power source
No.1
PDU Power A –48 VDC and RTN leadsTwo 18-AWG wire leads
Appropriate leads on power source
No.2
PDU Power B –48 VDC and RTN leadsTwo 18-AWG wire leads
1.
Task 1: Turning Off All CTP Platform Power | 112
2.
Task 2: Connecting the Grounding Cable to the CTP Platform (CTP2056 Platform Only) | 112
3.
Task 3: Connecting the Power Cables to the CTP2000 Platform | 113
Task 1: Turning Off All CTP Platform Power
Push all device power switches to OFF to turn off the device.
Task 2: Connecting the Grounding Cable to the CTP Platform (CTP2056 Platform Only)
The CTP2056 device has a grounding stud located in the rear of the chassis, near the power inputs.
To ground the power unit:
1. Locate the grounding stud.
2. Remove the nuts and locking washers from the grounding stud.
NOTE: We recommend a minimum of 18-AWG ground wire with a ring-style terminal.
3. Place the grounding cable lead on the grounding stud, and tighten the nuts to secure the connection.
4. Connect the other end of the ground cable to the appropriate ground termination lead.
112

Table of Contents

Other manuals for Juniper CTP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper CTP2000 Series and is the answer not in the manual?

Juniper CTP2000 Series Specifications

General IconGeneral
BrandJuniper
ModelCTP2000 Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals