Device size 24 26 27 28 29
Housing size U U U P P
Cooling mode (L=air; W=water) L L W L W L W
Number of modules for master/slave
Input data
Mains phases 3
Permitted mains forms TN system
Rated input voltage U
N / V 400
Input voltage range U
in / V 340…480 ± 0%
Mains frequency f
N / Hz 50 / 60 ± 2
Rated input power S
N / kVA 125 173 208 256 319
Rated input current I
N / A 180 250 300
1)
370 460
Max. permissible mains fuse type gR / aR
250 350 400 500 630
Output data
Rated output voltage U
outN_dc / V 680
Output voltage range
2)
U_dc / V 530…840
Overvoltageswitch-o󰀨(E.OP) U
OP_dc / V 840
Power supply/regenerative rated current
3)
IoutN_dc / A 180 250 300
4)
370 460
Max. regenerative DC current 30 s I
out_max_dc / A 270 313 375 462 575
Rated switching frequency f
SN / kHz 8 4 8 8 4
5)
4
5)
Max. switching frequency fS_max / kHz 8 8 8 8 4 4
Other data (referring to the rated data)
Overcurrentcut-o󰀨(E.OC) I
OC / % 180 150 150 150 150
Overload current (E.OL) 30 s I
OL / % 150 125 125 125 125
Max. permissible DC link capacity C
ext / mF 45 43 40 35 35
Max. AIC charging current (=> 6.5) I
AIC / A 226 226 226 98 98
Max. external charging current (=> 6.5) I
ext / A
Max. permissible total charging current (=> 6.5)
Ipre / A 226 226 226 98 98
Mains input circuit (=> 6.5) Type D1 D1
Permissible DC fuses => „DC fuses“
Short-circuit factor at the connection point (S
kn / SN) 15 < Skn“ / < 350
10 < Skn“ /
< 350
Power dissipation at rated operation P
BR / W 2230 2550 3500 4500 3000 3800
Max. heat sink temperature t
_max / °C 90 90 60 90 60 90
6) 7)
90
6)
1)
The input current of the
drive converter
must be limited to the rated current of the AIC / LCL lter, if
necessary.
2)
The operation is dependent on the voltage setpoint and the UOP limit (=> Programming manual).
3)
Measured at a reference voltage of 680 V DC.
4)
Limited by the rated current of the DC-terminal ! The input current must be limited to 300 A for input
voltages < 400 V.
5)
Must be set to 4 kHz for AIC operation (factory setting 2 kHz) !
6)
Special settings are required for this device sizes (Reduction of the max. heat sink temperature to
85°C, => Programming manual).
7)
Max. ambient temperature Ta of 35°C.
28
UNIT DATA

Table of Contents

Other manuals for KEB COMBIVERT F5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 Series and is the answer not in the manual?

KEB COMBIVERT F5 Series Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5 Series
CategoryDC Drives
LanguageEnglish

Related product manuals