TP-7070 8/20 13Section 1 Specifications and Features
Section 1 Specifications and Features
1.1 Introduction
The spec sheets for each generator set provide model-
specific generator and engine information. The
controller spec sheet provides specifications for the
controller. Refer to the respective spec sheet for data
not supplied in this manual. Refer to the generator set
service manual, installation manual, engine operation
manual, and engine service manual for additional
specifications.
1.2 Controller Specifications
1.2.1 Controller Specifications
Power Supply Requirements:
Nominal voltage: 24 VDC, reverse polarity
p
rotected
240 VAC/60Hz customer-supplied; factory wiring
to basic electrical package available
Operating Temperature:
- 40C to 70C (- 40F to 158F)
Storage Temperature:
- 40C to 70C (- 40F to 158F)
Humidity: 5% to 95% non-condensing
Protection Index:
IP65 Front
IP20 Rear
Standards:
NFPA 99
NFPA 110, Level 1
CSA 282-09
UL 508
IEC/EN60068-2-52 (salt spray)
CE Directive
1.2.2 Display and Touchscreen
Type: XGA TFT LED LCD
Screen Size: 305 mm (12 inches)
Viewing Angle: 140 h
orizontal and vertical
Languages: English, French
Note: Have setup and adjustments of the controller
performed only by an authorized Kohler
distributor. The setup and adjustments are
password protected.
1.3 Controller Features
The controller features include a 307 mm (12.1 inch)
t
ouchscreen with backlight and wide viewing angle (140
degrees horizontal and vertical) and terminal blocks for
input and output connections. See Figure 1-1 for an
illustration of the controller front panel and the customer
connection area. Controller features include:
12-inch touchscreen with backlight and wide viewing
a
ngle for easy local access to data.
System settings are password-protected.
Measurements selectable in metric or English units.
User language is selectable (English or French).
Graphic displays show generator set mechanical
values including operating hours, fuel level*, battery
voltage, coolant temperature, oil pressure, and oil
temperature.
Meter displays provide a visual representation of
generator electrical values including power (kW),
power factor, reactive power (kVAR), frequency,
voltage, and current (amps).
Two USB ports allow connection of a flash drive,
mouse, or keypad.
Electrical data, mechanical data, and system settings
can be saved to a flash drive.
Recording feature allows data collection of key
v
alues.
Ethernet port allows connection to a PC type
computer and/or Ethernet switch.
Serial (RS-485) port.
The controller supports Modbus RTU and TCP
protocols.
Real time clock with battery back-up.
See the controller specification sheet or operation
manual for input and output specifications.
Modbus is a registered trademark of Schneider Electric.
* Where applicable

Table of Contents

Other manuals for Kohler KD1750

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler KD1750 and is the answer not in the manual?

Kohler KD1750 Specifications

General IconGeneral
BrandKohler
ModelKD1750
CategoryInverter
LanguageEnglish

Related product manuals