TP-7070 8/2018 Section 1 Specifications and Features
1.6 Base Module Inputs and Outputs
The inputs and outputs on the base module are factory set. See Figure 1-7 and Figure 1-8 for base module input and
o
utput factory settings. For optional input/output module settings, see Section 4, Accessories.
Note: Make customer connections to TB10 in the connection box. See the generator set wiring diagram for details.
Inputs Factory Setting
Digital Inputs
DI0 Remote Start
DI1 Low Fuel Level Switch
DI2 Breaker Open Status
DI3 Remote Reset
DI4 Aux Shutdown
DI5 High Fuel Level Switch
DI6 Aux Warning
DI7 Low Oil Level
DI8 Battery Charger Fault
DI9 Fuel Leak Alarm
DI10 Idle Mode
DI11 GFCI Tripped
DI12 Remote Speed Adjust Enable
DI13 Key Switch Enable
DI14 Load Shed Enable
DI15 Overcrank Test
DI16 Reserved for Factory Use
DI17 Emergency Stop
Analog Input
AI0-
Remote Speed Adjust
(+/- 10 VDC)
AI0+
Resistive Input
RES0-
Ambient Air Temperature
RES0+
Figure 1-7 APM802 Base Module Input Factory Settings
Outputs
Output Relay
Configuration
Factory Setting
Digital Outputs
DO0 Form C Common Fault
DO1 Form C System Ready
DO2 Form C Common Warning
DO3 Form C Reserved for Factory Use
DO4 Form A Horn
DO5 Form A Low Coolant Temp Warning
DO6 Form A Shunt Trip
DO7 Form A Not in Auto
DO8 Form A BCA Excitation
DO9 Form A Generator Running
DO10 Form A EPS supplying Load
DO11 Form A ECU Fault Reset
DO12 Form A Low Oil Pressure
DO13 Form A High Coolant Temp
DO14 Form A Low Coolant Level Fault
DO15 Form A Low Fuel Level
DO16 Form A Start Button Illuminate
DO17 Form A Watchdog
Figure 1-8 APM802 Base Module Output Factory Settings