TP-7070 8/20 17Section 1 Specifications and Features
1.5 Parameter Settings
Controller parameter settings are factory-set and
p
assword-protected. Selected settings are shown in
Figure 1-6. If changes are required, contact your
distributor.
Parameter Setting
Preheat duration* 0 s
Air-preheater maximum delay
(at each start attempt)*
30 s
Number of starting attempts 3
Time between starting attempts 15 s
Fault inhibition time in starting phase 10 s
Auxiliaries start time 5 s
Generators starting maximum delay
(Dead Bus synchronizing)
5 s
Generator cooling time 300 s
(5 min.)
Generator immobilization time 5 s
Ventilation time after generator stopped 10 s
* Parameter settings not applicable for KD2000- KD4000
Figure 1-6 Factory Settings