104
FMS Fault Correction Correction input ( F )
Aids
F1 ___________________________________________________________________
Fault 121 The monitoring processor checks whether the present correction values
122 lies within the range set.
123 ___________________________________________________________________
124
125 Check correction range
Otherwise A7
_____________________________________________________________________________________________________
F2
Fault 301 Correction input is configured for 4 … 20 mA, but the instantaneous
302 value is < 4 mA, wire possibly broken or connection poles transposed
Check wiring
Check parameter 431, 432
_____________________________________________________________________________________________________
F3
Selector switch on LR1 on "Measure” Centre position potentiometer P4 on power unit LPE 1/S possibly set
incorrectly
at output 0…20 mA but no 10 mA (see LR 1 operating instructions)
at output 4…20 mA but no 12 mA
Turn potentiometer to 10 or 12 mA (on LPE 1/S)
_____________________________________________________________________________________________________
F4
A value other than The maximum correction range according to the standard software setting is
200 or +/-100 is displayed 200 points. Other range sizes are available for special cases, however.
_____________________________________________________________________________________________________
F5
50% is not displayed Either 10 or 12 mA are not being fed to the FMS
Measure current
Check wiring
Otherwise as for F2 or F3
or
Jumpers are incorrectly inserted on the back of the front panel.
Check
_____________________________________________________________________________________________________
F6
Fault 381 The values of the correction input signals are compared between main and
382 monitoring processor.
Change processor card

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals