62
FMS Commissioning O regulation
2
Operation
The meaning of the op O regulation on standby (during burner start-up), or O regulation
22
additional modes temporarily switched off via parameters 914 and 915 as a function of
load.
or O regulation active.
2
ot O regulation temporarily deactivated (air shortage, probe dynamics
2
etc).
od O regulation deactivated (perturbed), e.g. test routines failed during
2
burner start-up, dynamic test negative, O regulation temporarily
2
deactivated for over 1 hour etc.
Resetting od: Manually
Switch to "O regulation” mode.
2
Press the Acceptance key and call up error text.
Push key 3 (2) upwards Z error deleted.
ATTENTION: If deleting an error, the error text must always first be called
up by pressing the Acceptance key.
Automatic
During each new burner start-up.
Calling up O regulation
2
text messages
- Switch display to O regulation mode.
2
Selector switch (1) to "Status” and channel key 3 (2) upwards.
- Call up text messages by pressing the Acceptance key (3).
- Back Z press the Acceptance key (3) again,
or turn selector switch (1) to a different position.
xxx
LAMTECLAMTEC
xxx
xxx
xxx
- - - - or - - - -- - - - or - - - -
xxx
LAMTECLAMTEC
xxx
xxx
xxx
2
3
1
2
!
O regulation active
2

Table of Contents

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals