14
and a message will be displayed for the device on
the My Home menu option.
• Move device closer to the S40 thermostat or
add an Lennox Wireless Extender between the
sensor and thermostat.
• For wall placement, install room sensor at a minium
height of 5 feet (1.52 meters) on an interior wall.
See "Wall Mounting" on page 15 for illustration
example.
• Use the provided wall template when mounting
sensor to the wall.
• For sensor desktop/table placement use the
provided stand.
• For eective temperature sensing, mount the
sensor in a location enabling it to sense the general
room environment. The sensor must NOT be:
» Blocked from normal air circulation by ob-
structions (e.g., behind curtains or cubicle
walls).
» Exposed to articial heat sources (e.g., lights,
computers, copiers, or coee makers) or to
sunlight (at any time of the day).
» Exposed to direct sunlight.
» Exposed to drafts from windows, doorways,
diusers, or returns.
» Exposed to air ow through the conduit (e.g.,
from leaks in plenum ducts) or other holes
into the wall cavity.
» Mounted on an exterior wall.
» Mounted on or near a large thermal mass
(e.g., a concrete block wall).
NOTE: The above factors primarily aect tempera-
ture sensing, but some also aect accurate
humidity and occupancy sensing as well.
» If the device is out of range of your S40 ther-
mostat a blue light will turn on.
• For eective occupancy detection, determine a
location that will maximize the area of detection in
a room.
» The smart room sensor occupancy detec-
tion function has a 100 degree horizontal
span and a 32 degree vertical span. Improper
placement may limit the area of occupancy
detection for the sensor.
» Large rooms may require more than one sen-
sor to ensure occupancy detection. Please
see "Figure 9. Occupancy Sensor Detection
Pattern Examples" on page 19 for ex-
amples of optimal mounting locations for the
smart room sensor.