Table 57. Menu Interface (Level 1 - SETUP)
Level 2 Level 7Level 6Level 5Level 4Level 3
TEST &
BALANCE
BLOWER
BLOWER HEATING HIGH = XXXX CFM
BLOWER COOLING HIGH = XXXX CFM
BLOWER COOLING LOW = XXXX CFM
BLOWER VENTILATION = XXXX CFM
ON (TARGET XXXX CFM) ADJUST BLOWER RPM = XXXX RPM
AUTO CALIBRATE = START CALIBRATION OR
CALIBRATION DONE
STARTING BLOWER > BLOWER ON >
CLOSING DAMPER > PROGRESS % WILL
BE DISPLAYED. WILL RETURN TO AUTO
CALIBRATE SCREEN AFTER REACHING
100%. PRESS THE ADJUST AND SET
VALUE BUTTON FOR THE OPTION =
CALIBRATION DONE. PRESS SAVE TO
CONTINUE. RESULTS OF CALIBRATION
ARE AVAILABLE IN SERVICE REPORT.
DAMPER
DAMPER FDBK CALIB > IS DAMPER
CLOSED?
YES OR NO
NOTE: INSTALLER WILL NEED TO
VISUALLY INSPECT THE DAMPER TO
ENSURE THAT IT IS CLOSED.
MIN DAMPER POSITION > BLOWER ON
HIGH =
XX %
MIN DAMPER POSITION > BLOWER ON
LOW=
X %
ECONOMIZER TEMP ECON TYPE = TEMPER
ATURE OFFSET OR TEMPERATURE SETPT
NOTE: THIS OPTION IS DEPENDANT ON
CONFIGURATION ID 1 SETUP.
ECONOMIZER OAT SETPOINT = XX.X F.
ECONOMIZER ENTHALPY SETPOINT = XX
MA
NOTE: THESE OPTIONS ARE DEPENDANT
ON CONFIGURATION ID 1 SETUP.
ECONOMIZER ENTHALPY OFFSET = XX MA
FREE COOLING SUPPLY AIR SETPOINT = XX.X F
DAMPER OUTDOOR AIRFLOW = XXX CFM
ADVANCED AIRFLOW ALARMS = ENABLED
OR DISABLED (ONLY VISIBLE IF CONFIGUR
ATION ID 1, POSITION 2 IS SET CORRECTLY).
ADV AIRFLOW ALARMS LO SPLY AIR
FLOW ALM = XX%
ADV AIRFLOW ALARMS LO OD AIRFLOW
ALM = XX%
ADV AIRFLOW ALARMS HI OD AIFLOW
ALM = XX%
ADV AIRFLOW ALARMS ALM TRIGGER
PERIOD = XXXX SEC
VENTILATION OPTIONS
DEMAND CONTROL VENTILATION
BUILDING PRESSURE CONTROL
IF DCV
DEMAND CONTROL VENT > DAMPER
START OPEN = XXX PPM
DEMAND CONTROL VENT > DAMPER
FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT > DAMPER
MAX OA CFM = X CFM
(ONLY VISIBLE IF CONFIGURATION ID 1,
POSITION 2 IS SET CORRECTLY).
DEMAND CONTROL VENT > DAMPER
MAX OPENING = XXX.X %.
IF BPC
BUILDING PRESS CTROL > PRESSURE
SETPOINT = X.X IN H20.