29
5.5.3. Energence C Box High and Ultra-High Efficiency Units (13-, 15- and 20-Ton)
Table 20. Low Ambient Fan Operations (C Box Standard, High and Ultra-High Efficiency Units)
Models Fan
Associated
Compressor
Low Ambient Control OD Temp
< Parameter 84 (55°F)
LCH, LGH 156H
1 1, 2, 3 On with S11 or S84 or S85
2, 3 1, 2, 3 OFF
LCH, LGH 180H
1 1, 3 On with S11, S84 or S85
2 1, 3 OFF
3 2, 3 On with S84 or S85
4 2, 3 OFF
LCH, LGH 180U and 240U
1 1, 2 OFF
2 1, 2 OFF
3 1, 2 ON with S11
4 3, 4 ON with S85
5 3, 4 OFF
6 3, 4 OFF with S85
Compressor 1 and 2 use S11 and compressor 3 and 4 would use S85.
C BOX
Gas / Electric & Electric / Electric
LC/LG 156H 13 Ton
1 2 3
A55−K1
A55−K2
A178−K14
1 (B4)
S84
CONDENSER FANS
2 (B5)
55ºF
3 (B21)
55ºF
COMPRESSORS
ANY−A55−K10
ANY−A55−K68
ANY−A55−K68
S85
S11