101
Table 57. Menu Interface (Level 1 - SETUP)
Level 2 Level 7Level 6Level 5Level 4Level 3
OUTDOOR AIR CONTROL (ONLY VISIBLE IF
CONFIGURATION ID 1, POSITION 8 IS SET
CORRECTLY)
VELOCITY SETPOINT = XXX FT/MIN
POWER EXHAUST ON BY ECON TRAVEL = XX.X %
FRESH AIR HEATING
ENABLE FAH = NO OR
YES
FRESH AIR HEATING FAH SETPOINT = XX F
FRESH AIR COOLING
ENABLE FAC = YES OR
NO
FRESH AIR COOLING AFC SETPOINT = XX F
NOTE: PARAMETERS AVAILABLE ARE DEPENDENT ON MODEL NUMBER AND CONFIGURATION ID 1 AND 2 SETTINGS.
24.2.4. Service
Table 58. Menu Interface (Level 1 - SERVICE)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION.
TEST MENU SECTION: EACH MAJOR COMPONENT OF THE M3 UNIT CONTROLLER WILL INCLUDE A TEST MODE TO VERIFY CRITICAL
COMPONENT AND SYSTEM PERFORMANCE. ALL BLOWER TESTING WILL REMAIN ACTIVE FOR TWO HOURS UNLESS TERMINATED BY
THE USER.
Level 1 Level 2 Level 3
Use the Adjust and set values
arrows to scroll up or down for
selection options.
WHEN SELECTED (PRESS BACK TO RETURN TO
THE PREVIOUS MENU)
SERVICE TEST
COOL
OPTIONS ARE COOL 1, COOL
2, COOL 3 AND COOL 4.
COOL X ODN
RAT: XX.X F
DAT: XX.X F
(if advanced airflow is enabled then ACTUAL CFM is
displayed.)
or
NOT APPLICABLE EQUIPMENT NOT PRESENT
HEAT
OPTIONS ARE HEAT 1, HEAT
2, HEAT 3 AND HEAT 4.
HEAT X ON
RAT: XX.X F
DAT: XX.X F
(if advanced airflow is enabled then ACTUAL CFM is
displayed.)
or
NOT APPLICABLE EQUIPMENT NOT PRESENT
BLOWER
BLOWER HI BLH ON/OFF SET POINT
BLOWER LOW BLL ON/OFF SET POINT
PROVING SWITCH PSW CLOSED/OPEN SET POINT
BLOWER
FILTER SWITCH FSW CLOSED/OPEN SET POINT
RPM XX RPM FSW CLOSED/OPEN SET POINT
SPEED XX RPM TD: XX (IF COMPRESSOR IS TURNED ON)
DAMPER
POSITION
ACTUAL: 0.1%.
NOTE: THIS FUNCTION IS ONLY AVAILABLE IF
CONFIGURATION ID 1, POSITION 2 HAS BEEN
CONFIGURED.
EXHAUST 1 OR 2
SET ON/OFF SETPOINT (EX1 OR EX2 ON/OFF
ACTUAL)
FANS
FAN 1 (OR FAN L) FN1 (OR FL) ON/OFF SETPOINT
FAN 2 (OR FAN H) FN2 (OR FH) ON/OFF SETPOINT
FAN 3 THROUGH 6. ON/OFF
DEHUMIDIFIER
OPTIONS ARE HUM 1 AND
HUM 2
WHEN SELECTING OPTION, RESPONSE WILL BE
EITHER DEHUMIDIFIER X ON OR NOT APPLIC
ABLE EQUIPMENT NOT PRESENT.