NOTE: Additional settings will be required to complete the configuration after entering the baud rate.
16.8. Comfort Sensors
BacNet Configuration
To enable the M3 Unit Controller to use Comfort Sensors, use the following procedure:
1. Confirm that the Configuration ID 1, position 5 has been set to B as mentioned in the previous section.
2. Go to SETUP and select NETWORK INTEGRATION.
3. Use the Adjust and set values arrows to display BACNET and press the SAVE button to continue.
4. Adjust the BACNET ADDRESS if required and press SAVE button to continue.
5. Adjust the BACKNET BAUD RATE if required and press SAVE button to continue.
6. CONTROL MODE will need to be set to ROOM SENSOR. Press the SAVE button to continue.
7. NETWORK SENSOR > CO2 needs to be set to NO. Press the SAVE button to continue.
8. NETWORK SENSOR > RELATIVE HUMIDITY needs be set to NO. Press the SAVE button to continue.
9. NETWORK SENSOR > TEMPERATURE will need to be set to NO (mandatory).
NOTE: Additional settings will be required to complete after completing step 9. Once the above steps are completed the
Comfort Sensor output will be accepted by the system.
L Connection Configuration
1. Go to SETUP and select NETWORK INTEGRATION.
2. Use the Adjust and set values arrows to display L-CONNECTION and press the SAVE button to continue.
3. Adjust the L-CONNECTION ADDRESS if required and press SAVE button to continue.
NOTE: Both the L-Connection address setting and Comfort Sense address setting needs to be exactly the same. In
addition, the Comfort Sense should be configured with NO NCP option.
4. CONTROL MODE will need to be set to ROOM SENSOR. Press the SAVE button to continue.
5. NETWORK SENSOR > CO2 needs to be set to YES if needed. Press the SAVE button to continue.
6. NETWORK SENSOR > RELATIVE HUMIDITY needs be set to YES (mandatory). Press the SAVE button to
continue.
7. NETWORK SENSOR > TEMPERATURE will need to be set to YES (mandatory).
NOTE: Additional settings will be required to complete after completing step 7. Once the above steps are completed the
Comfort Sensor output will be accepted by the system.
NOTE: If Comfort Sensor input is still not working, cycle power to the M3 Unit Controller.