Table 63. M3 Control Parameters
Control Parameter
DescriptionUnits
Control Value
No DescriptionUnitsMax.DefaultMin.
Parameter Short
Description
Screen Name
12 MSAV SMK CFM
Multi-Stage Air Volume
Smoke Detection Mode
(Alarm)
450
Check unit
parameter label
as default may
be altered at
factory test.
14400 CFM
Multi-Stage Air Volume Smoke
Detection Mode (Alarm)
NOTE: In order for the SMOKE
CFM change to take affect, go
the SETUP > TEST & BAL
ANCE > BLOWER and run the
the wizard. Performing this task
will recalculate the output to the
desired CFM. No adjustments
are required during this proced
ure.
19 MAX CFM RPM
Maximum Cubic Feet
Per Minute Revolutions
Per Minute
445
Check unit para
meter label as
default may be
altered at fact
ory test.
1780 RPM
Maximum Cubic Feet Per
Minute Revolutions Per Minute
27 MIN OUPT CL VT SMK
Minimum Output Cooling
Vent Smoke Detection
Mode (Alarm)
30.0 50.0 100.0 %
Minimum Output Cooling Vent
Smoke Detection Mode (Alarm)
28 MIN OUTPUT HEAT Minimum Output Heat 30.0 50.0 100.0 % Minimum Output Heat
29 MIN DAMPER BLOWER Minimum Damper Blower 0.0
Check unit para
meter label as
default may be
altered at fact
ory test.
101.0 %
Setting this parameter to
101.0% will disable this feature.
30
PWREXH STG2 MIN
BLR
Power Exhaust Stage 2
Minimum Blower
0.0 70.0 100.0 %
Power Exhaust Stage 2 Minim
um Blower
31 SUPPLY PID P CONST
Supply Proportional
Base Control Loop for
Variable Air Volume or
Constant Air Volume with
Bypass Damper
0 17 127 Counts
Variable Air Volume or Constant
Air Volume with Bypass
Damper supply PID Proportion
al constant.
32 SUPPLY PID I CONST
Supply Integral Base
Control Loop for Variable
Air Volume or Constant
Air Volume with Bypass
Damper
0 12 127 Counts
Variable Air Volume or Constant
Air Volume with Bypass
Damper supply PID Integral
constant.
33 SUPPLY PID D CONST
Supply Derivative Base
Control Loop for Variable
Air Volume or Constant
Air Volume with Bypass
Damper
0 0 127 Counts
Variable Air Volume or Constant
Air Volume with Bypass
Damper supply PID derivative
constant.
34
BLR STC PRESS SMK
SP
Constant Air Volume with
Bypass Damper Static
Pressure Set Point
During Smoke Alarm
0 1 5 w.c.
Constant air volume with by
pass damper static pressure set
point during smoke alarm.
35 BLR STC PRES VT SP
Constant Air Volume with
Bypass Damper Static
Pressure Set Point for
Ventilation
0 1 5 w.c.
Constant air volume with by
pass damper static pressure set
point for ventilation.
36 BLR STC PRES HT SP
Constant Air Volume with
Bypass Damper Static
Pressure Set Point for
Heating
0 1 5 w.c.
Constant air volume with by
pass damper static pressure set
point for heating
37 BLR STC PRES CL SP
Constant Air Volume with
Bypass Damper Static
Pressure Set Point for
Cooling
0 1 5 w.c.
Constant air volume with by
pass damper static pressure set
point for cooling