EasyManuals Logo
Home>Lennox>Controller>PRODIGY2.0

Lennox PRODIGY2.0 User Manual

Lennox PRODIGY2.0
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
40
Table 29. 4-Compressor Humiditrol Default Operation (using 2stage Thermostat)
Demands Condition Unit Operation
Free Air Damper
(Economizer)
Reheat
Valve 1
Reheat
Valve 2
Thermostat
Humidity
Sensor
Trigger OAS
Compressor
Blower Speeds
Vent
Cool
C1
Cool
C2
Cool
C3
Cool
C4
Heat
1 2 3 4
G Unoccupied OFF OFF OFF OFF X Closed OFF OFF
G Occupied OFF OFF OFF OFF X Minimum OFF OFF
Y1 Damper position Suitable OFF OFF OFF OFF X
Modulate up to
Maximum
OFF OFF
Y2 Damper position Suitable OFF OFF OFF OFF X
Modulate up to
Maximum
OFF OFF
Y2
Damper position
and maximum
position and
time.
Suitable ON ON OFF OFF X Maximum OFF OFF
Y1
Not
Suitable
ON ON OFF OFF X Minimum OFF OFF
Y2
Not
Suitable
ON ON ON ON X Minimum OFF OFF
Dehum ON ON OFF OFF X Minimum ON ON
Y1 Dehum ON ON ON ON X Minimum ON ON
Y2 Dehum ON ON ON ON X Minimum OFF OFF
W OFF OFF OFF OFF X Minimum OFF OFF