Installation
4-17
L MA9300PLC EN 1.4
• Observe the max. permissible motor cable length:
V
r
= 400 V (+10%) V
r
= 480 V (+10%)
Type f
chop
=8kHz f
chop
=16kHz f
chop
=8kHz f
chop
=16kHz
9321
/
//
/
9322 up to 50 m up to 45 m up to 50 m up to 25 m
9323 - 9332 up to 50 m up to 50 m up to 50 m up to 50 m
The max. permissible motor cable length of types 9323 - 9332 will be reduced if the motor cable has more than a single
core.
• Two parallel single cores: L
max
=17m
• Three parallel single cores: L
max
=9m
• Connect motor cables to screw terminals U, V, W.
– Ensure correct pole connection.
– Maximum motor cable length: 50 m.
– Max. permissible cable cross-sections and screw tightening torques:
Max. permissible cable cross-sec-
tions
Tightening torques for terminals
Type
Power connec-
tions
T1, T2 U, V, W PE connection
Screen/
Strain relief
T1, T2
9321 - 9326 4mm
21)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb-in)
3.4 Nm
(30 lb- in)
9327 - 9329 25 mm
22)
1.5 mm
2
5Nm(44lb-in)
M4: 1.7 Nm (15 lb-in)
0.5 ... 0.6 Nm
9330 - 9331 95 mm
22)
.
15 Nm (132 lb-in)
5: 3.4 Nm
30 lb-in
4.4...5.3 lb-in
9332 120 mm
22)
30 Nm (264 lb-in)
1)
with pin cable lug: 6 mm
2
with wire crimp cap: 4 mm
2
2)
with ring cable lug: Cross-section is only limited by cable duct in the housing
Tip!
Switching on the motor side of the controller is only permitted for emergency switch-off.
4.2.7.3 Connection of a brake unit
• When connecting a brake unit (brake module with internal brake resistor or brake chopper
with external brake resistor) observe the corresponding Operating Instructions in any case.
Stop!
• Design the circuit so that, if the temperature monitoring of the brake unit is activated,
– the controllers are inhibited (X5/28 = LOW).
– the mains is disconnected.
• Examples:
– Chapter 4.3, “Installation of a CE-typical drive system”.
(^ 4-33)
– Fig. 4-9, “Decentralized supply for DC-bus connection of several drives”. (^ 4-18)