Troubleshooting and fault elimination
6-2
L
MA9300PLC EN 1.4
6.2 Reset of error messages
Reaction on
operating errors
Measures for re-commissioning Danger notes
TRIP/ FAIL-QSP • After the error has been eliminated, the drive can be restarted when an
acknowledgement has been sent.
• TRIP / FAIL-QSP acknowledgement by:
– Global-Drive-Control: Click ”Trip reset” in dialog box ”Diagnostics
9300”.
(“Working with the history buffer”)
– Keypad 9371 BB:
Press STOP key. Then press RUN to enable the controller again.
– Fieldbus module: Set C0043 = 0
– Control word C0135
– Terminal X5/E5 (default setting) or “DCTRL-TRIP-RESET”
– Control word AIF
– Control word system bus (CAN)
If a TRIP source is still active, TRIP cannot be
reset.
Message • After having eliminated the error, the message is reset automatically.
The drive restarts automatically, if the error is
eliminated.
War nin g • After eliminating the fault, the warning is reset automatically.