Table 10: ACR Copper Tubing Dimensions and Physical Characteristics
1-4
.
Nominal Pipe
Outside
'LDPHWHULQ
Actual Outside
'LDPHWHULQ
'UDZQ7HPSHU Annealed Temper
Nominal Wall
7KLFNQHVVLQ
:HLJKWOEIW
Cubic ft per
Linear ft
Nominal Wall
7KLFNQHVVLQ
:HLJKWOEIW
Cubic ft per
Linear ft
1/4 0.250 -- -- -- 0.030 0.081 .00020
3/8 0.375 0.030 0.126 .00054 0.032 0.134 .00053
1/2 0.500 0.035 0.198 .00101 0.032 0.182 .00103
5/8 0.625 0.040 0.285 .00162 0.035 0.251 .00168
3/4 0.750 0.042 0.362 .00242 0.042 0.362 .00242
7/8 0.875 0.045 0.455 .00336 0.045 0.455 .00336
1-1/8 1.125 0.050 0.655 .00573 0.050 0.655 .00573
1
All dimensions provided are in accordance with ASTM B280 – Standard.
2
Design pressure = 551 psig.
3
ACR Tubing is available as hard drawn or annealed (soft) and are suitable for use with R410A refrigerant.
4
The Copper Tube Handbook, 2010, Copper Development Association Inc., 260 Madison Avenue, New York, NY 10016.
Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.
Prevent dust, water or other contaminants from entering the piping during installation. Contaminants can cause mechanical failure.
LG Engineered Y-branch Kits and Header Kits
LG Y-branch and Header kits are highly engineered devices designed to evenly divide the flow of refrigerant, and are used to join one pipe
segment to two or more segments.
No Substitutions
2QO\/*VXSSOLHG<EUDQFKDQG+HDGHU¿WWLQJVFDQEHXVHGWRMRLQRQHSLSHVHJPHQWWRWZRRUPRUHVHJPHQWV7KLUGSDUW\RU¿HOGIDEULFDWHG
7HH¶V<¿WWLQJV+HDGHUVRURWKHUEUDQFK¿WWLQJVDUHQRWTXDOL¿HGIRUXVHZLWK/*0XOWL96V\VWHPV7KHRQO\¿HOGSURYLGHG¿WWLQJVDOORZHGLQ
a Multi V S piping system are 45° and 90° elbows.
Table 11: Y-Branches and Headers.
Y-branch Kit Model No
Headers
4 branch 7 branch
ARBLN01621 ARBL054 ARBL057
ARBLN03321 ARBL104 ARBL107
If the diameter of the branch pipe segments differ from that of the designated refrigerant piping, trim to the desired section using a pipe
cutter, and then use an adapter to connect.
$OZD\VIROORZPDQXIDFWXUHU¶VJXLGHOLQHVRQUHIULJHUDQWSLSLQJUHVWULFWLRQVVXFKDVPD[LPXPOHQJWKHOHYDWLRQGLIIHUHQFHDQGGLDPHWHUV
Failure to do so can result in reduced heating / cooling performance or equipment malfunction.
Y-Branch Kits
LG Y-branch and kits are highly engineered devices designed to evenly divide the flow of refrigerant, and are used to join one pipe seg-
PHQWWRWZRRUPRUHVHJPHQWV7KHUHLVRQO\RQHW\SHRI<EUDQFKXVHGLQ/*0XOWL6V\VWHPV<EUDQFKHVXVHGZLWKWKHLQGRRUXQLWVLQWKH
refrigerant piping system at each transition. Field-supplied “T” fittings or “Y” branches will not be accepted. Do not install Y-branches
EDFNZDUGVUHIULJHUDQWIORZFDQQRWPDNH8WXUQVWKURXJK<EUDQFKHV7KHHTXLYDOHQWSLSHOHQJWKRIHDFK<EUDQFKƍPXVWEHDGGHGWR
each pipe segment entered into LATS piping design software.
LG Y-Branch Kits Consist of:
Y-branches: For heat pump systems - one liquid line and one vapor line (two [2] total).
Reducer fittings as applicable.
0ROGHGFODPVKHOOW\SHSHHODQGVWLFNLQVXODWLRQFRYHUV
Install Correctly
Y-branches can be installed upstream between the Header and the outdoor unit, but a Y-branch cannot be installed between a header
and an indoor unit.
To avoid the potential of uneven refrigerant distribution through a header fitting, minimize the difference in equivalent pipe length be-
tween the header fitting and each connected indoor unit.
Piping Preparation
GENERAL INSTALLATION GUIDELINES

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V S ARUN048GSS4 and is the answer not in the manual?

LG MULTI V S ARUN048GSS4 Specifications

General IconGeneral
BrandLG
ModelMULTI V S ARUN048GSS4
CategoryAir Conditioner
LanguageEnglish

Related product manuals