41
Refrigerant Piping Connections
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
REFRIGERANT PIPING CONNECTIONS
7KHV\VWHPZLOOVWRSRSHUDWLRQGXHWRH[FHVVLYHRULQVXI¿FLHQWUHIULJHUDQWWKHUHIRUHDOZD\VFKDUJHWKHXQLWSURSHUO\:KHQVHUYLFLQJDOZD\V
refer to any notes about system piping length and additional refrigerant amounts.
Refrigerant Charge
1
CF (Ref.) = Correction Factor for Refrigerant Charge.
2
For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).
3
0D[LPXPTXDQWLW\RILQGRRUXQLWVDOORZHG$581 $581 $581
4
If trim charge is negative, remove refrigerant. If trim charge is positive, add refrigerant.
6\VWHP7DJRU,'BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
BB
-RE1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
3URMHFW0DQDJHUBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
'DWHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
Line # 'HVFULSWLRQ &KDVVLV,' Size Quantity &)5HI
1
7RWDOOEV
1 Linear feet of 1/4" liquid line tubing
2
²² 0.015
2 Linear feet of 3/8" liquid line tubing
2
²² 0.041
3 Linear feet of 1/2" liquid line tubing
2
²² 0.079
4 Linear feet of 5/8" liquid line tubing
2
²² 0.116
5 Linear feet of 3/4" liquid line tubing
2
²² 0.179
6 Linear feet of 7/8" liquid line tubing
2
²² 0.238
7 Linear feet of 1" liquid line tubing
2
²² 0.323
8 Art Cool Gallery SF 9k to 12k 0.22
9 :DOO0RXQWHG$UW&RRO0LUURU SB, SE 5k to 15k 0.53
10 :DOO0RXQWHG$UW&RRO0LUURU SC 18k to 24k 0.62
11 :DOO0RXQWHG SV 30k to 36k 1.01
12 1-Way Cassette TU 7k to 12k 0.44
13 1-Way Cassette TT 18k to 24k 0.64
14 2-Way Cassette TL 18k to 24k 0.35
15 4-Way 2' x 2' Cassette TR 5k to 7k 0.40
16 4-Way 2' x 2' Cassette TR 9k to 12k 0.55
17 4-Way 2' x 2' Cassette TQ 15k to 18k 0.71
18 :D\¶[¶&DVVHWWH TNA 7k to 24k 0.89
19 4-Way 3' x 3' Cassette TPC 24k to 28k 1.06
20 :D\¶[¶&DVVHWWH 70$ 24k to 36k 1.08
21 4-Way 3' x 3' Cassette TNC 36k 1.41
22 4-Way 3' x 3' Cassette 70& 42k to 48k 1.41
23 High Static Ducted BH 7k to 24k 0.57
24 High Static Ducted BG 7k to 42k 0.97
25 High Static Ducted BR 28k to 54k 1.37
26 High Static Ducted B8 36k to 96k 2.2
27 Low Static Ducted L1 7k to 9k 0.31
28 Low Static Ducted L2 12k to 18k 0.42
29 Low Static Ducted L3 24k 0.55
30 Low Static Ducted Bottom Return B3 7k to 15k 0.37
31 Low Static Ducted Bottom Return B4 18k to 24k 0.82
32 Vertical / Horizontal Air Handling Unit NJ 12k to 30k 1.04
33 Vertical / Horizontal Air Handling Unit NJ 36k 1.57
34 Vertical / Horizontal Air Handling Unit NK 42k to 54k 2.00
35 Ceiling Suspended VJ 18k to 24k 0.77
36 &RQYHUWLEOH6XUIDFH0RXQW²&HLOLQJ:DOO VE 9k to 12k 0.22
37 Floor Standing CE (U) 7k to 15k 0.37
38 Floor Standing CF (U) 18k to 24k 0.82
39 Additional Refrigerant Charge Required
40 ARUN038GSS4 Outdoor Unit Factory Refrigerant Charge
3
38k 6.6
41 ARUN048GSS4 Outdoor Unit Factory Refrigerant Charge
3
48k 6.6
42 ARUN053GSS4 Outdoor Unit Factory Refrigerant Charge
3
53k 6.6
43 7RWDO6\VWHP&KDUJH6XPRI$GGLWLRQDO5HIULJHUDQW&KDUJH5HTXLUHGDQG7RWDO)DFWRU\5HIULJHUDQW&KDUJH
4