$GMXVWLQJ7DUJHW3UHVVXUH)XQFWLRQ
Set Outdoor Unit PCB DIP Switch No. 5 to ON.
6HOHFWWKHPRGHXVLQJWKHŹDQGŻEXWWRQV
Choose “Func” by pushing the
Ɣ button.
Target pressure is set.
6HOHFWWKHIXQFWLRQXVLQJWKHŹDQGŻEXWWRQV
Choose “Fn8” by pushing the Ɣ button.
6HOHFWWKHRSWLRQXVLQJWKHŹDQGŻEXWWRQV
Choose “Heat” or “Cool” by pushing the Ɣ button.
6HOHFWWKHRSWLRQXVLQJWKHŹDQGŻEXWWRQV
Choose “op1” ~ “op4” by pushing the Ɣ button.
Mode
Purpose
Condensing
Temperature
9DULDWLRQ
Evaporating
Temperature
9DULDWLRQ
Heat Cool
op1
Increase
Capacity
Increase
Capacity
+3.6°F
(+2°C)
-5.4°F (-3°C)
op2
Decrease
Power
Consumption
Increase
Capacity
-3.6°F
(-2°C)
-2.7°F
(-1.5°C)
op3
Decrease
Power
Consumption
Decrease
Power
Consumption
-7.2°F
(-4°C)
+4.5°F
(+2.5°C)
op4
Decrease
Power
Consumption
Decrease
Power
Consumption
-10.8°F
(-6°C)
-8.1°F
(-4.5°C)
Table 43: Adjusting Target Pressure Function Settings.