MULTI V S System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ring Terminal
Power Wiring
Power Wiring Connection Guidelines
Best practice dictates using ring or spade terminals to terminate power wiring at the power
terminal block
.
To Install a Ring Terminal:
1. Trim the strand wiring with wire cutters or pliers, then strip the insulation to expose the
strand wiring to about 3/8 inch.
2. Using a ring terminal fastener or pliers, securely clamp a ring terminal to each stripped
wire end.
Figure 58: Close up of a Typical Ring Terminal
3RZHU6XSSO\3RZHU:LULQJ6SHFLILFDWLRQV
0XOWL96RXWGRRUXQLWDQGWKHLQGRRUXQLWVPXVWREWDLQSRZHUIURPVHSDUDWHEUHDNHUV
Multi V S systems operate at 1Ø, 208-230V, 60Hz
Multi V indoor units operate at 1Ø, 208-230V, 60Hz. (Indoor units draw minimal power. Where permitted by National Electrical Code and
local codes, it may be prudent to connect multiple indoor units to a properly sized breaker.)
3RZHUVXSSOLHVZLUHW\SHVDQGVL]HVVKRXOGEHVHOHFWHGEDVHGRQ1DWLRQDO(OHFWULFDO&RGHDQGORFDOFRGHV0D[LPXPDOORZDEOHYROWDJH
fluctuation ±10% or nameplate rated value.
Properly ground the outdoor unit and indoor units per National Electrical Code and local codes.
For power to the outdoor units, use copper wiring that is solid or stranded, and shielded with the wires separately insulated.
*URXQGZLUHVKRXOGEHORQJHUWKDQWKHFRPPRQSRZHUFRPPXQLFDWLRQZLUHV
Connect the wiring firmly so the wires cannot be easily pulled out.
Refer to the inside of the chassis cover for circuit and terminal block diagrams for your model unit.
Always match color codes of each wire and follow wiring diagram.
Outdoor unit wiring can be found on the inside of the outdoor unit control cover.
Figure 59: Schematic of Suggested Power Wiring / Communication Cable System.
Breaker or Fused
Disconnect Switch
Pull Box(Installer Option)
: Single Phase Power Supply (L1, L2)
: Communications Cable for Wired Controllers
: Communication Cable Between Outdoor Units and Indoor Units
Breaker or Fused
Disconnect Switch
Power supply
1 Phase
208-230V
60 Hz
Power supply
1 Phase
208-230V
60 Hz
WIRING
3RZHU:LULQJ6SHFL¿FDWLRQV
If ring terminals or spade clips are not available, then:
When terminating wires of the same thickness, follow the instructions demonstrated in the illustrations.
)LUPO\DWWDFKWKHZLUHVHFXUHLQDZD\WRSUHYHQWH[WHUQDOIRUFHVIURPEHLQJLPSDUWHGRQWKHWHUPLQDOEORFN
Use an appropriately sized screwdriver for tightening the terminals.
Do not over tighten the connections; over-tightening may damage the terminals.
'RQRWWHUPLQDWHGLIIHUHQWJDXJHZLUHVWRWKHSRZHUWHUPLQDOEORFN6ODFNLQWKHZLULQJPD\JHQHUDWHKHDWDQG¿UHZKLFKPD\UHVXOWLQSK\VLFDO
injury or death.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V S ARUN048GSS4 and is the answer not in the manual?

LG MULTI V S ARUN048GSS4 Specifications

General IconGeneral
BrandLG
ModelMULTI V S ARUN048GSS4
CategoryAir Conditioner
LanguageEnglish

Related product manuals