Wiring
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
WIRING
Outdoor Unit Power Wiring and Cable Connections
For power wiring, use solid or stranded that must comply
with all local and national electrical codes.
Connect the communications cable between indoor units
using a daisy chain configuration only. “Star” or “home run”
control wiring connections involving soldering or wire caps
are not permitted.
For communications cable, use 18 AWG, two-conductor,
stranded, shielded or unshielded. If shielded, must be
grounded to the chassis at the outdoor unit only.
Provide separate conduits for control wiring and power
wiring.
Power and communications cables must not be routed
in the same conduit and must be routed in a manner that
keeps them a minimum of two (2) inches apart.
Connect outdoor unit terminal IDU-A to the odd numbered
indoor unit terminal. Terminal “A” on the indoor units may
be tagged 3(A) or 5(A).
Connect outdoor unit terminal IDU-B to indoor unit termi-
nal “B”. Terminal “B” on the indoor units may be tagged
3(B) or 5(B).
0D[LPXPDOORZHGOHQJWKRILQGRRUXQLWFRPPXQLFDWLRQ
cable is 984 feet.
Figure 57: Communications Wiring Terminals.
1
2
3
4
5
6
7
8
9
10
GND
Fan Only/Cool/Heat Selector
6ZLWFK²3URYLGHVPDQXDORYHU-
ride of microprocessor selected
PRGHRIRSHUDWLRQ²KHDWLQJ
cooling, or fan only
Central Control and Building
Automation System Communi-
FDWLRQ%XV&RQQHFWLRQ²&RQ-
nect LG Central Controller
DQG%06JDWHZD\SURGXFWV
,QGRRU8QLWV²&RPPXQLFDWLRQ
Bus Connection
1RWXVHGZLWK0XOWL96
1 2 V
Power source for
selected controllers
Ground
SODU-B
DRY 2
DRY1
Internet A
Internet B
IDU-A
IDU-B
SODU-A
Detail of the Power Wiring and Communications Cable Connections

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V S ARUN048GSS4 and is the answer not in the manual?

LG MULTI V S ARUN048GSS4 Specifications

General IconGeneral
BrandLG
ModelMULTI V S ARUN048GSS4
CategoryAir Conditioner
LanguageEnglish

Related product manuals