PCB Component S/W No. Set Up
No. 1 Manual Addressing Valve No. 1
No. 2 Manual Addressing Valve No. 2
No. 3 Manual Addressing Valve No. 3
No. 4 Manual Addressing Valve No. 4
SW03M Increases the Valve Address by Ten (10)
SW04M Increases the Valve Address by One (1)
SW05M Manual Addressing of Zoned Indoor Units
1
12 43
ON
OFF
2
3
4
SW01M
6:06:06:0',3DQG7DFW6ZLWFKHVIRU0DQXDO9DOYH
Addressing, continued.
Zoning
• Set the address of the heat recovery unit valve to the central control address of the connected indoor unit.
• SW01M: Select the valve to address.
• SW03M: Increases the valve address by ten (10).
• SW04M: Increases the valve address by one (1).
• SW05M: Rotary switch
• Indoor units must be addressed first with a central control address.
• Each indoor unit must have a unique, preset central control address (using its wired controller) before manual valve addressing can occur.
Table 57: Settings for Manual Valve Addressing, Zoning.
HEAT RECOVERY UNIT SETTINGS