83
Outdoor Unit Functions
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Cycle Data View (SE8)
Cycle Data View displays the cycle data of the operating outdoor
unit. Cycle Data View can display 26 different cycle datapoints on
the SSD.
For use on both heat pump and heat recovery systems.
Turn No. 5 on the master outdoor unit PCB
DIP switch bank SW01 to ON.
6HOHFWWKH³6YF´PRGHE\XVLQJWKH6:&IRUZDUGŹEXWWRQDQGWKH
6:&EDFNZDUGŻEXWWRQDQGWKHQSUHVVWKH6:&FRQILUP
ƔEXWWRQ
6HOHFWWKH³6(´IXQFWLRQE\XVLQJWKH6:&IRUZDUGŹEXWWRQDQG
WKH6:&EDFNZDUGŻEXWWRQDQGWKHQSUHVVWKH6:&
FRQILUPƔEXWWRQ
Select from “oP1” through “oP26” by using the SW03C forward
ŹEXWWRQDQGWKH6:&EDFNZDUGŻEXWWRQDQGWKHQSUHVV
WKH6:&FRQILUPƔEXWWRQ
Figure 34: Setting the Cycle Data View Function.
The Cycle Data View function begins. See table below for “oP1”
through ‘oP26” option information.
Option Description Display Example seg_1 seg_2 seg_3 seg_4
op1 Current High Pressure P1 4,320.9 kPA (626.7 psi) 4321
op2 Current Low Pressure P2 1,234.2 kPA (179 psi) 1234
op3 Inv 1 Pulse h1 120 Hz 1 2 0
op4 Inv 2 Pulse h2 30 3 0
op5 Fan RPMs h3 110 1 1 0
op6 Degree of Subcooling T1 5.3°C (41.5°F) 5 3
op7 Degree of Superheating T2 -4.5°C (23.9°F) - 4 5
op8 Outdoor Unit Temperature T3 10°C (50°F) 1 0 0
op9 Suction Temperature T4 43.4°C (110.1°F) 4 3 4
op10 Compressor 1 Discharge Temperature T5 150°C (302°F) 1 5 0
op11 Compressor 2 Discharge Temperature T6 124°C (255.2°F) 1 2 4
op12 Liquid Pipe Temperature T7 10°C (50°F) 1 0 0
op13 Sc_in T8 10°C (50°F) 1 0 0
op14 Sc_out T9 10°C (50°F) 1 0 0
op15 Hex_total T10 10°C (50°F) 1 0 0
op16 Hex_hi T11 10°C (50°F) 1 0 0
op17 Hex_low T12 10°C (50°F) 1 0 0
op18 Inlet Pipe Temperature of Indoor Unit T13 -10°C (14°F - 1 0 0
op19 Main 1 EEV PLS1 1,940 1940
op20 Main 2 EEV PLS2 32 3 2
op21 SC EEV PLS3 16 1 6
op22 Oil EEV PLS4 50 5 0
op23 vi eev 1 PLS5 1,350 1350
op24 vi eev 2 PLS6 8 8
op25 Operation Capacity of Indoor Units IDU1 24,000 2 4
op26 Total Number of Indoor Units IDU2 10 1 0
Table 44: Cycle Data View Datapoint Options.
OTHER CONTROLS
Setting Optional Modes