PROTECTION CONTROL
Pressure Protection Control
Pressure Protection Control
Pressure Control in Cooling Mode
Pressure Range Compressor Fan
3GSVL Stop Stop
Pd > 547.5 psi -15 Hz / 10 seconds 530VHFRQGV
3GSVL Frequency Hold* 530VHFRQGV
3GSVL +]RUOHVVVHFRQGV 530VHFRQGV
Pd < 504.7 psi Normal Control
Table 12: High Pressure Control in Cooling Mode.
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).
Table 13: Low Pressure Control in Cooling Mode.
Pressure Range Compressor Fan
3VSVL Stop (one [1]) minute later) Stop
3VSVL -15 Hz / 10 seconds -100 RPM / 10 seconds
Ps > 21.8 psi Frequency Hold* -100 RPM / 10 seconds
Ps > 23.2 psi +]RUOHVVVHFRQGV -100 RPM / 10 seconds
Ps > 27.6 psi +]RUOHVVVHFRQGV -100 RPM / 10 seconds
Ps > 31.9 psi Normal Control
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).
Pressure Control in Heating Mode
Pressure Range Compressor Fan
3GSVL Stop Stop
Pd > 495.3 psi -15 Hz / 10 seconds -50 RPM / 10 seconds
Table 14: High Pressure Control in Heating Mode.
Table 15: Low Pressure Control in Heating Mode.
Pressure Range Compressor Fan
3VSVL Stop Stop
3VSVL -15 Hz / 10 seconds 530VHFRQGV
3VSVL Frequency Hold* 530VHFRQGV
3VSVL +]RUOHVVVHFRQGV 530VHFRQGV
3VSVL Normal Control Normal Control
* Frequency Hold = Frequency (or RPM) is not increasing (can decrease).