EasyManuals Logo
Home>Midea>Air Conditioner>VRF

Midea VRF Service Manual

Midea VRF
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
MCAC-VTSM-2016-05 One-way Cassette
Indoor Unit 3
2. Specifications
Model
MDV-D18Q1/VN1-D
MDV-D22Q1/VN1-D
Power supply
V- Ph-Hz
220-240V~1Ph~60Hz
Capacity
kW
1.8
2.2
Btu/h
6100
7500
Input
W
41
41
Rated current
A
0.24
0.24
Capacity
kW
2.2
2.6
Btu/h
7500
8900
Input
W
41
41
Rated current
A
0.24
0.24
Model
RPS12B
Type
AC motor
Brand
Welling
Input(H/M/L)
W
29.5/26.7/25.0
29.5/26.7/25.0
Capacitor
μF
0.8μF/450V
0.8μF/450V
Speed (H/M/L)
r/min
1180/955/710
Number of rows
2
2
Tube pitch(a) × row pitch(b)
in.(mm)
53/64×17/32(21×13.37)
53/64×17/32(21×13.37)
Fin spacing
in.(mm)
1/16(1.5)
1/16(1.5)
Fin type
Hydrophilic aluminum
Tube outside dia. and type
in.(mm)
9/32(Ф7) Inner groove tube
Coil length × height × width
in.(mm)
29-59/64×9-15/16×1-3/64(760×252.4×26.74)
Number of circuits
2
2
Indoor air flow (H/M/L)
m
3
/h
523/404/275
CFM
308/238/162
Indoor noise level (H/M/L)
dB(A)
37/34/30
38/34/30
Dimension (W×D)
in.(mm)
41-1/2×6-1/32×16-47/64(1054×153×425)
Packing (W×D)
in.(mm)
45-15/32×9-41/64×19-19/64(1155×245×490)
Net/Gross weight
lbs. (kg)
27.8/35.3(12.5/16)
27.8/35.3(12.5/16)
Dimension (W×D)
in.(mm)
46-29/64×63/64×18-5/16(1180×25×465)
Packing (W×D)
in.(mm)
48-1/2×4-7/32×20-23/64(1232×107×517)
Net/Gross weight
lbs. (kg)
7.7/11.5(3.5/5.2)
7.7/11.5(3.5/5.2)
Refrigerant type
R410A
Throttle
Type
Electronic expansion valve
Model
D20MISZ-1R(L)
Design pressure(H/L)
MPa
4.4/2.6
Liquid side
in.(mm)
1/4(Ф6.35)
Gas side
in.(mm)
1/2(Ф12.7)
Power wiring
mm
2
1.0
Signal wiring
mm
2
0.75
Drainage water pipe diameter
in.(mm)
OD 63/64 (Ф25)
Controller
Wireless remote controller
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB,19°CWB,
outdoor temperature:35°CDB,equivalent refrigerant piping: 8m(horizontal).
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB,
outdoor temperature: 7°CDB,6°CWB,equivalent refrigerant piping: 8m(horizontal)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF and is the answer not in the manual?