Appendix B: Compatible Devices
FA-106 and FA-103 Underwriters Laboratories Canada ULC Listed 2-Wire Smoke
Detectors
Notes:
• Reset time, hold for five seconds minimum.
• Total standby current of all detectors must not exceed 3 mA.
• Two-wire smoke detectors can be mixed or matched with different models on the
same Initiating Circuit as long as the total standby current of all detectors does not
exceed 3mA.
Make Model / Base
Maximum # of
devices per
circuit
Make Model / Base
Maximum # of
devices per
circuit
Mircom System Sensor i3
MIR-525 30 C2W-BA c/w base 30
MIR-525T 30 C2WT-BA c/w base 30
Apollo System Sensor
Series 60A Bases 45681-200,-220,-232,-251 1400A 30
Series 65A Bases 45681-255,-256,-257,-258 2400A 25
55000-325 30 1451A/B401BA 25
55000-326 30 2451A/B401BA 25
55000-327 30 1100 25
55000-328 30 1151A/ B110LPA 25
Hochiki 1151A/ B116LPA 25
DCD-135/HSC-220R 12 1451A/B401A 25
DCD-135/NS6-220 12 1451A/ B406BA 25
DCD-190/HSC-220R 12 1451DH/ DH400 25
DCD-190/NS4-220 12 2100A 30
DCD-190/NS6-220 12 2100TA 30
SU-24/HSC-220R 12 2151A/ B110LPA 15
SU-24/NS4-220 7 2151A/ B116LPA 25
SU-24/NS6-220 7 2400THA 25
SLR-24/HSC-220R 12 2451A / B401BA 25
SLR-24/NS4-220 12 2451A / B406BA 25
SLR-24/NS6-220 12 2451A / DH400 25