50
Field Wiring
Figure 32 Main Fire Alarm Module Terminal Connections (continued)
Notes: The terminal blocks are "depluggable" for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Notes: All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
Indicating (NAC) circuits are fully supervised and rated for 24 VDC unfiltered
1.7A max. Use wire size as stated in Table 15 NAC Circuit Wiring Table on
page 63.
BELL, HORN, OR
STROBE
Legend: See Appendix A for compatible devices.
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
IND2+ (Z)
IND2- (Z)
IND2- (Y/Z)
SUPERVISED INDICATING CIRCUIT #2
INDICATION
CIRCUIT 1
(POWER
LIMITED)
IND1+ (Z)
STYLE Z
(CLASS A)
WIRING
IND1- (Y/Z)
IND1+ (Y/Z)
IND2+ (Y/Z)
IND1- (Z)
INDICATION
CIRCUIT 2
(POWER
LIMITED)
INDICATING CIRCUITS 3 & 4
ARE NOT SHOWN
STYLE Y
(CLASS B)
WIRING
SUPERVISED INDICATING CIRCUIT #1
ANALOG
LOOP 2
CONNECTIONS
(LOOP 0 AND
LOOP1 ARE
INTERNAL
ADDRESSES
FOR FIRST 8
CARDS AND
SECOND 8
CARDS
RESPECTIVELY
+
4-WIRE
POWER
SUPPLY
-
+
AUX.
POWER
-
TRB
RTI
INTERFACE
TRL
ANALOG LOOP FIELD WIRING
(CLASS A OR B)
SEE ANALOG LOOP WIRING SECTION
CONNECTION TO MIRCOM RTI
REMOTE TROUBLE INDICATOR
(SEE RTI INSTALLATION
INSTRUCTION) BLK TOTRB+ BLU
TO TRL-RED & WHT TO AUX.
POWER COM+
END OF LINE RELAY
LISTED S3403
MODEL A77-716B
MANUFACTURED BY
SYSTEM SENSOR
2
3
41
6
5
+
-
+
-
TO
INITIATING
CIRCUIT
+
-
+
-
POWER
+
-
DETECTION
4-WIRE
DETECTION
DEVICE
AUXILIARY POWER
FOR REMOTE ANNUNCIATORS
24 VDC UNFILTERED
1.7 AMPS MAXIMUM
RTI
BLK
BLU
RED & WHT
LOOP 2
B
A
+
-
+
-
+
-
-
+
+
+
-
-
NAC