58
Field Wiring
8.3 NAC Signal Module (SGM-1004A) Terminal Connections
Wire devices to terminals as shown in Figure 40. For further wiring information 8.8 Wiring
Tables and Information. For specifications 12.0 Appendix A: Specifications. For compatible
devices 13.0 Appendix B: Compatible Devices.
Figure 40 Hardwire Signal Module Terminal Connections
Notes: The terminal blocks are “depluggable” for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
SGM-1004A NAC circuits are fully supervised and rated for 24 VDC unfiltered
1.7A max. They must use wire size as stated in the wiring tables on page 63.
IND2+ (Z)
IND2- (Z)
IND2- (Y/ Z)
SUPERVISED INDICATING CIRCUIT #2
INDICATION
CIRCUIT 1
(POWER
LIMITED)
IND1+ (Z)
STYLE Z
(CLA SS A)
WIRING
IND1- (Y/ Z)
IND1+ (Y/ Z)
IND2+ (Y/ Z)
IND1- (Z)
INDICATION
CIRCUIT 2
(POWER
LIMITED)
STYLE Y
(CLA SS B)
WIRING
SUPERVISED INDICATING CIRCUIT #1
IND4+ (Z)
IND4- (Z)
IND4- (Y/ Z)
SUPERVISED INDICATING CIRCUIT #4
INDICATION
CIRCUIT 3
(POWER
LIMITED)
IND3+ (Z)
STYLE Z
(CLA SS A)
WIRING
IND3- (Y/ Z)
IND3+ (Y/ Z)
IND4+ (Y/ Z)
IND3- (Z)
INDICATION
CIRCUIT 4
(POWER
LIMITED)
STYLE Y
(CLA SS B)
WIRING
SUPERVISED INDICATING CIRCUIT #3
Le ge nd : See Appendix B for compatible devices.
SMOKE DETECTOR
3.9K 1/2W ELR LISTED S5434
MODEL MP-300
MANUFACTURED BY MIRCOM