90
Appendix B: Compatible Devices
13.6 FX-2000 Series Compatible Hardwire Smoke Detectors (ULC)
Note: Whether mixing different models of compatible smoke detectors or using the
same model on the same circuit, the total standby current of all detectors must
not exceed 3 mA.
Table 30 FX-2000 Series Compatible Hardwire Smoke Detectors (ULC Listed)
Make & Model # of Devices
/Circuit
Make & Model # of Devices
/Circuit
Hochiki Simplex
DCD-135/NS6-220 30 2098-9110 base
DCD-135/NS4-220 30
Mirtone
DCD-135/HSC-220R 30 73471 base
DCD-190/NS6-220 30 73494 base
DCD-190/NS4-220 30 73575 base
DCD-190/HSC-220R 30 73495/73486 base
SIJ-24/NS6-220 30 73495/73487 base
SIJ-24/NS4-220 30 73595/73486
SIJ-24/HSC-220R 30 73595/73497
SLR-24/NS6-220 30 73594/73400
SLR-24/NS4-220 30 73405/73400
SLR-24/HSC-220R 30 73594/73401
SLR-24H/NS6-220 30 73405/73401
SLR-24H/NS4-220 30
System Sensor
SLR-24H/HSC-220R 30 1400-A 30
SLR-835/NS6-220 30 2400-A 25
SLR-835/NS4-220 30 1451-A/B401B 25
SLR-835/HSC-220R 30 1451-A/B406B 25
SLR-835B-2 30 2451-A/B401B 25
Cerberus Pyrotronics
2451-A/B406B 25
D1-2 1451DH/DH400A 30
D1-3/DB-3S 30 2451-A/DH400A 25
Mircom
1151A 30
MIR-525 30 2151A 30
MIR-525T 30 C2W-BA/C2WT-BA 30
MIR-1400A 30 C2WTR-B 1
MIR-2400A 25 C2WTA-BA 1
MIR-752L 21
NAPCO
MIR-752HL 21 FW-2 30