72
Operation
11.0 Operation
The following chapter describes operation of the FX-2000 Series FACPs including:
Single Stage Operation
Two Stage Operation
Pre-Signal Operation
UUKL Feature
Output Circuit Delay Operation
Circuit Types
Initiating (Detection) Circuit Type
NAC (Signal) Circuits Types
Evacuation Codes
11.1 Single Stage Operation
In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following: non-verified alarm, verified alarm, sprinkler alarm, water-flow alarm, and
general alarm circuits. Any of these alarm inputs occurring when the panel is not already in
alarm cause the following:
The buzzer sounds steadily
If fire drill is active, it is cancelled
The Common Alarm LED turns on
The Common Alarm relay activates if Aux disconnect is not active
The Auto Signal Silence timer, if configured, starts
The Signal Silence Inhibit timer, if configured, starts
All non-disconnected NAC programmed to the input are activated provided that Aux
disconnect is not active
Non-disconnected strobes associated with the input are activated
Non-disconnected signals associated with the input are activated at the evacuation rate
Subsequent alarms when the panel is already in alarm, cause the following:
The alert buzzer sounds steadily
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options
must be limited to specific values or not used at all as indicated below.
Program feature or option Permitted in UL 864? (Y/N) Possible settings Settings permitted in UL 864
Delay Output Timer YES
4 seconds maximum (due
to worst case loop delay of
6 seconds)
10 seconds
Monitor Buzzer NO
Sounding at the Fast Rate
or OFF
OFF

Table of Contents

Other manuals for Mircom FX-2000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FX-2000 series and is the answer not in the manual?

Mircom FX-2000 series Specifications

General IconGeneral
BrandMircom
ModelFX-2000 series
CategoryControl Panel
LanguageEnglish

Related product manuals