-17-
(e) HI POWER Heating operation (HI POWER button on remote controller: ON)
High rotate speed operation for15 minutes.
● Detail of operation
Inverter instruction frequency
Heat-retaining mode (max. 9th speed)
Corresponding to instruction frequency
Notes: (1) Room temperature can’t be adjusted during the HI POWER operation.
(2) Priority is given to actuation of protective device even during the HI POWER operation.
4.7 Outline of cooling operation
(1) Operation of functional components
Item
Functional component
Instruction frequency
other than 0
Becomes 0 due to
abnormal stop
OFF (Indoor continuous
instructions-0)
(2) Air flow switching
(a) The inverter instruction frequency changes within the range of selected air flow.
Corresponding to frequency
(b) When the protection device is actuated, operation is performed in the corresponding mode.
(c) Outdoor fan operates in accordance with the instruction frequency.
(3) Details of control in each operating mode
(a) Fuzzy operation
Deviation between the room temperature setting compensation value and the suction air
temperature is calculated in accordance with the fuzzy rule, and used for control of the air
flow and the inverter frequency.
(b) Cooling constant temperature operation
● Operating conditions
If the frequency obtained with the fuzzy calculation drops below -24 rps during the
cooling fuzzy operation, the operation changes to the cooling constant temperature
operation.
● Detail of operation
Inverter instruction
frequency
According to the Indoor Fan Operating Mode Table (corresponding to fan speed)