1.3.10
The acceleration/deceleration time increases.
Item
Cause
Check
The torque limit command
D
Check that the CON1 pin No.5
1
is issued.
(TLl)
or No.21(TL2) are
turned on by referencing
Appendix l-4 or 1-5.
Remedy
o
Turn off the limit command
input TLl and TL2 to re-
lease the torque limit.
The
Ea
ROM No. is
o
Check the
E'
ROM No. by
o
Replace the ROM with a cor-
2
incorrect.
referencing Appendix 11
rect one or change the
Table 1.1.
related parameter.
3
The parameter
(#33CSN)
o
Check the parameter by
value is too large.
referencing Reference
1.2.2.
o
Correctly change the para-
meter value.
-
53
-