6. BASIC INSTRUCTIONS
6 26
MELSEC-A
(3) At (S), (S1), (S2) and D, 0 to 99999999 (BCD 8 digits) can be specified.
(4) Even if the addition result exceeds 99999999, the carry flag does not turn on
and the carry digit is ignored.
DB-
(1) Subtracts the BCD data specified at (S) from the BCD data specified at (D), and
stores the subtraction result into the device specified at (D).
(2) Performs subtraction of the BCD data specified at (S1) and the BCD data
speci-fied at (S2), and stores the subtraction result into the device specified at
(D1).
Digits higher than the specified digit are regarded as 0.
(3) At (S), (S1), (S2) and (D), 0 to 99999999 (BCD 8 digits) can be specified.
(4) It is required to judge whether the operation result is positive or negative by use
of the program.
Execution Conditions
Digits higher than the specified digit are regarded as 0.
OFF
ON
Executed
per scan
Executed
per scan
Executed
only once
Executed
only once
P
Addition/subtraction
commands

Table of Contents

Other manuals for Mitsubishi MELSEC-A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A series and is the answer not in the manual?

Mitsubishi MELSEC-A series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A series
CategoryController
LanguageEnglish

Related product manuals