EasyManuals Logo
Home>Mitsubishi>Controller>MELSEC-A series

Mitsubishi MELSEC-A series Programming Manual

Mitsubishi MELSEC-A series
508 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
5. SEQUENCE INSTRUCTIONS
5 9
MELSEC-A
5.2.2 Operation result push, read, pop
(MPS, MRD, MPP)
Available Device
Bit device Word (16-bit) device Constant Pointer Level
Carry
flag
Error
flag
X Y M L S B F T C D W R A0 A1 Z V K H P I N
Digit specification
Index
M9012 (M9010, M9011)
Functions MPS
(1) Stores the operation result (ON/OFF) immediately preceding the MPS
instruction.
(2) The MPS instruction can be used up to the number of times mentioned below.
For AnA, A2AS, AnU, QCPU-A (A Mode) and A2USH board : 16 times
For CPUs other than AnA, A2AS, AnU, QCPU-A (A Mode) and A2USH board
: 12 times
However, it can be used 11 times consecutively in ladder mode. If an MPP
instruction is used in between, 1 is reduced from the number of used MPS
instructions.
MRD
(1) Reads the operation result stored by the MPS instruction, and resumes the
operation with that operation result, starting at the next step.
Applicable
CPU
All CPUs
MPS
MRD
MPP
When the ladder is dispiayed, MPS, MRD, and MPP
are omitted.

Table of Contents

Other manuals for Mitsubishi MELSEC-A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A series and is the answer not in the manual?

Mitsubishi MELSEC-A series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A series
CategoryController
LanguageEnglish

Related product manuals