5. SEQUENCE INSTRUCTIONS
5 28
MELSEC-A
5.4 Shift Instructions
5.4.1 Bit device shift (SFT, SFTP)
Available Device
Bit device Word (16-bit) device Constant Pointer
Level
Carry
flag
Error
flag
X Y M L S B F T C D W R A0 A1 Z V K H P I N
Digit specification
Index
M9012 (M9010, M9011)
(D) O O O O O O
*1: Index qualification can be used with AnA, A2AS, AnU, QCPU-A (A Mode) and A2USH board only.
Functions (1) This instruction shifts the ON/OFF status of a device number, (defined as D-1)
to the device specified as D and turns off the device with the lower number.
(2) Turn on the head device to be shifted with the SET instruction.
(3) When the SFT or SFTP instruction is used consecutively, program higher device
numbers first. (See below.)
Setting data
*1
Applicable
CPU
All CPUs
SFT
SFTP
(D)
(D)
SFT instruction
1)
2)
3)
4)
5)
6)
7)
After the second shift input
X2 ON
After the first shift input
X2 ON
After the third shift input
After the fourth shift input
After the fifth shift input
Shift range
*: At M8 to 15, 1 indicates ON and 0 indicates OFF.
Shift input
M0
X002
P
SFT M14
P
SFT M13
P
SFT M12
P
SFT M11
SFT M10
(D)
Device number to be
shifted

Table of Contents

Other manuals for Mitsubishi MELSEC-A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A series and is the answer not in the manual?

Mitsubishi MELSEC-A series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A series
CategoryController
LanguageEnglish

Related product manuals