9 - 21
ERROR CODE LIST9.
Table 9.4 Error Code List for the AnU, A2AS and A2USH board (Continue)
Error Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause Corrective Action
"PARAMETER
ERROR"
(Checked at
power on and at
STOP/PAUSE
RUN.)
11 111 STOP Capacity settings of the main and sub
programs, microcomputer program, file
register comments, status latch, sampl-
ing trace and extension file registers
are not within the usable range of the
CPU.
Read parameters in the CPU memory,
check the contents, make necessary
corrections and write them again to the
memory.
112 Total of the set capacity of the main and
sub programs, file register comments,
status latch, sampling trace and
extension file registers exceeds
capacity of the memory cassette.
113 Latch range set by parameters or
setting of M, L or S is incorrect.
114 Sum check error
115 Either of settings of the remote RUN/
PAUSE contact point by parameters,
operation mode at occurrence of error,
annunciator indication mode, or STOP
RUN indication mode is incorrect.
116 The MNET-MINI automatic refresh
setting by parameters is incorrect.
117 Timer setting by parameters is
incorrect.
118 Counter setting by parameters is
incorrect.
"MISSING END
INS."
(Checked at
STOP RUN.)
12 121 STOP The ( ) instruction is not
given in the main program.
Write the instruction at the end of
the main program.
122 The ( ) instruction is not
given in the sub program if the sub
program is set by parameters.
Write the instruction at the end of
the sub program.
123 (1) When subprogram 2 is set by a
parameter, there is no ( )
instruction in subprogram 2.
(2) When subprogram 2 is set by a
parameter, subprogram 2 has not
been written from a peripheral
device.
124 (1) When subprogram 3 is set by a
parameter, there is no ( )
instruction in subprogram 3.
(2) When subprogram 3 is set by a
parameter, subprogram 2 has not
been written from a peripheral
device.
END FEND END
END FEND END
END FEND
END FEND