6
FUNCTIONS
6.9 Hardware Error Time PLC Operation Settings
6 - 41
1
Overview
2
Performance
Specification
3
Sequence Program
Configuration and
Execution Conditions
4
I/O Nunber Assignment
5
Memories and Files
Handled by CPU Module
6
Functions
7
Communication using
built-in Ethernet ports of
CPU module
8
Communication with
Intelligent Function
Module
6.9 Hardware Error Time PLC Operation Settings
(1) Hardware Error time PLC Operation Mode Setting
The hardware error time PLC operation mode setting is to set whether the operation
of the CPU module will be stopped or continued when a hardware error occurs in the
intelligent function module or interrupt module.
(2) Hardware Error time PLC Operation Mode Setting
Make the hardware error time PLC operation mode setting in the I/O assignment
setting of the PLC parameter dialog box.
1) Make I/O assignment setting.
2) Select the button.
3) Choose the hardware error time PLC operation mode of the slot to which the
hardware error time PLC operation mode is set.
(The default is "Stop".)
(3) Precautions
The hardware error time PLC operation mode setting is made valid when:
• When the PLC is powered OFF and then ON
• When the CPU module's RESET switch is set to neutral position
Figure 6.25 Hardware error time PLC operation setting sequence
Detailed setting
3) Hardware error time PLC operation
mode Select "Stop" or "Continue".
1) Make I/O assignment. 2) Select Detailed setting.