1 SAFETY
Mitsubishi Diesel Engine S16R & S16R2 OPERATION & MAINTENANCE MANUAL
63
Pub. No. K29001-00320 Revision: 1
Measures in the Event of
Emergency
Emergency Stop Procedure
Thoroughly understand the stopping procedure to
be followed in the event of emergency.
1 Use the emergency stopping devices
of the generator
"Emergency
Stopping Devices Installed During
Manufacturing the Generator" (→
Page 64).
2 If the engine will not stop, pull the
manual stop lever of this engine in
the direction of stopping and hold
this position.
Fig. 1-9 Emergency Stop Procedure
• The location of the manual stop lever
varies depending on the specification
of the engine. Refer to
"Protection
System - Location" (→ Page 82).
3 After the engine has stopped
completely, release the manual stop
lever.
When stopping the engine by pulling
the manual stop lever, keep pulling
the lever until the engine stops
completely.
* Otherwise, the engine may start again.
If the stop switch of the generator will
not function and the engine will not
stop by using the manual stop lever,
shut off fuel supply.
* Otherwise, the extent of damage may increase.