NAPCO Security Group
NAPCO Gemini C-Series Control Panel Programming Instructions--Volume 1
Page 18 Programming Instructions, Volume 1
FUNCTION MENU -- FIRE KEYPAD
The GEMC-FK1 Fire keypad Function Menu provides access to a variety of Fire system utility functions. Some func-
tions listed below may or may not appear, depending on the type of Code used to enter the Function Menu (see
"Security, Program & User Codes" on page 15). For the Burglary Keypad Function Menu, see page 21.
1. Unlock a Fire keypad with either a Master Security Code, Dealer Keypad Pro-
gram Code or a Fire User Code as detailed in UNLOCKING THE FIRE KEYPAD
on page 17. Press MENU.
2. Scroll forward or backward through the functions using NEXT and PRIOR,
respectively.
3. To select and execute a function, press ENTER.
To return to normal keypad operation, press RESET. Note: The keypad will
automatically exit the Function Menu if no activity is detected for longer than 1
minute.
B=A
P=B
Q=C
G=D
ZONE DIRECTORY: Displays the description of each fire zone in the system.
Press NEXT and PRIOR to scroll through list of fire zones.. Allows zones to be dis-
abled or enabled by pressing SILENCE (DISABLE) when viewing the selected
zone.
ZONE DISABLE: Displays disabled fire zones. Press NEXT and PRIOR to scroll
through list of disabled zones. Pressing SILENCE while viewing selected zone will
un-disable the displayed zone.
OUTPUT DIRECTORY: Displays a listing of the motherboard outputs and up to 40
external output relays and NAC boards in the system. Press NEXT and PRIOR to
scroll the zone directory. Allows outputs to be disabled or enabled by pressing the
SILENCE (DISABLE) button when viewing the selected output.
OUTPUT DISABLED: Displays disabled notification circuits. Press NEXT and
PRIOR to scroll through list of disabled notification circuits. Pressing SILENCE
(DISABLE) while viewing selected notification circuit will un-disable the dis-
played circuit.
LOCK KEYPAD: Master Security Code or Dealer Keypad Program Code or Fire User Code required to view this
function
) Immediately locks keypad. Must unlock with key or code to affect system
operation.
DISPLAY FIRE LOG: Displays all fire events in chronological order; use NEXT
and PRIOR buttons to scroll through the log.
DO FIRE DRILL: Activates a fire drill by forcing the programmed fire drill zone into
alarm.
DO ONE MAN TEST: (Master Security Code or Dealer Keypad Program Code required to view this function).
Initiates One Man Test mode (refer to page 14).
TEST COMMUNICATOR: (Master Security Code or Dealer Keypad Program Code required to view this func-
tion
). Initiates a test report to the central station.
DISPLAY ZONE
DIRECTORY Y/N
DISPLAY ZONES
DISABLED Y/N
DISPLAY OUTPUT
DIRECTORY Y/N
DISABLE
OUTPUT Y/N
LOCK
KEYPAD Y/N
DISPLAY FIRE LOG
Y/N
DO FIRE DRILL
Y/N
DO ONE MAN TEST
Y/N
TEST
COMMUNICATOR Y/N
GEMC-FK1 Fire Keypad